CyberPower OL6KRTF uninterruptible power supply (UPS) Double-conversion (Online) 6 kVA 5400 W 10 AC outlet(s)
- Form factor: Rackmount/Tower
- Product colour: Black
- UPS topology: Double-conversion (Online)
- Output power capacity: 6 kVA
- Output power: 5400 W
- Compliance certificates: RoHS
All 68 specificationsProduct page at cyberpowersystems.com ↗
Where to buy
We're not tracking prices for this product yet. Check current prices directly at:
We may earn a commission when you buy through links on this page — at no extra cost to you. Learn more
About this product
The CyberPower Smart App Online OL6KRTF is a combined 8U with a 6U rack/tower double-conversion UPS and a 2U step-down transformer to support 120 V and 200-240 V output requirements. It provides sine wave output to multiple types of critical IT infrastructure requiring seamless power protection. Generator-compatible, the OL6KRTF delivers consistent output power with zero transfer time. Automatic-bypass ensures connected equipment continues to operate seamlessly when an overload or internal fault is detected.
The OL6KRTF features a removable LCD control panel to reposition it in a more convenient location (with optional DB-26 cable) and it has a RMCARD205 pre-installed network card. Smart Battery Management charging technology increases battery life by up to 50%. Fast Charge Technology helps replenish battery charge from 0-90% in four hours regardless of number of Extended Battery Modules (EBM) connected. The energy-saving GreenPower UPS ECO Mode allows the UPS to reach up to 96% efficiency to reduce power consumption and thermal dissipation.
This UPS can use the BP240V30ART3U or BP240VL3U01 Extended Battery Module for more runtime. The OL6KRTF comes with a three-year warranty (including batteries) and a $300,000 Connected Equipment Guarantee.
Double-Conversion Topology
Provides consistent, clean, and nearly perfect sine wave output power, regardless of the condition of input power. UPS systems with this technology operate on isolated DC power 100% of the time and have a zero-transfer time because they electronically switch to battery (vs. using relays which can take 4-12 ms to switch). Double-conversion UPS systems are designed for high-availability applications, precise output voltage regulation (±2%), generator set compatibility, environments with poor power quality, and other sensitive electronic equipment.
Sine Wave Output Provides power protection to ENERGY STAR 6.0 systems with Active PFC power supplies.
Step-down Transformer
Converts 208V input voltage originating from utility power, a UPS, or a generator to 120V output. The included 6-foot cord (NEMA L6-30P plug to ROJ) connects the transformer to input power. Over temperature protection safeguards it from damage if the internal heat exceeds safe operating parameters.
Removable LCD Control Panel
Panel displays 24 UPS status readings and allows configuration of 27 operation settings. The onboard event log will record and display the five most recent UPS system events. The LCD control panel can be removed and mounted in a more convenient location, up to ten feet away from the UPS (with optional DB-26 cable). Users can manage, setup, and control various operation settings, users can scroll through multiple UPS status readings and run select UPS diagnostic tests.
Multiple Language Options
The LCD control panel can be configured to English, Spanish, French, or German for use in multiple countries.
Extended Battery Module (EBM)
Add runtime by connecting more EBMs. The Smart App Online series of UPS systems allow for up to ten EBMs to be connected in a daisy-chain.
Fast Charge Technology
Enables Smart App Online UPS systems with multiple EBMs to charge batteries from 0-90% capacity in four hours. This is possible thanks to the built-in charger in each EBM.
Smart Battery Management (SBM)
Extends the service life of Smart App Online UPS batteries and reduces excessive heat during charge cycles by using a three-stage charging process. The first stage charges the battery to full capacity. The second stage enters float mode. The third stage turns the charger OFF to allow the batteries to naturally discharge (rest) for up to 27 days or until they reach a low-voltage set point. SBM continuously monitors the UPS to restart the charge cycle as needed, ensuring that runtimes are maintained.
GreenPower UPS ECO Mode
Improves UPS efficiency up to 96% to reduce electrical and cooling costs.
Hot-Swappable Batteries
Eliminate downtime related to UPS maintenance for continuous power availability.
Generator Compatible
Mode of operation in which the UPS disregards rapid changes in input frequency like those found in the output waveform of some generator sets. This allows the UPS to continue to operate in normal Online Mode vs. switching to Battery Mode when the power source is a generator set.
Converter Mode
Provides the ability to set the UPS output frequency (50 Hz or 60 Hz), regardless of the input frequency. This is beneficial where the connected equipment must operate on a different frequency than provided by local electric utility.
Local and Remote Management
Monitor and manage the UPS system locally via USB or serial connection, or remotely via the pre-installed RMCARD205 network card. Access UPS status, configuration settings, event logs, and status records, and more. User can also setup email notifications.
Rack or Tower Installation
All the hardware accessories to rack mount the UPS in a standard 4-post 19” rack, or install as a tower unit, is included at no extra cost.
PowerPanel Business Edition Software
A robust and feature rich power monitoring and management tool for physical or virtual environments, PowerPanel Business Edition offers local (Agent) or remote (Client) functionality to automate graceful shutdown of IT equipment. Installing PowerPanel Business Edition Center provides centralized monitoring and management of PPBE Agents and Clients on the local network in addition to all CyberPower devices. PPBE is FREE for download on the Downloads tab above.
Three-Year Warranty
CyberPower will repair or replace a defective UPS system (including batteries) within three years of the purchase date.
Connected Equipment Guarantee
CyberPower will repair or replace properly connected equipment if it is damaged by a power surge.
Documents
- ManualUser manual ↗
- BrochureProduct Brochure ↗
Specifications
Key specifications
- Form factorThe shape or design of the product.
- Rackmount/Tower
- Product colourThe colour e.g. red, blue, green, black, white.
- Black
- UPS topologyThe two main UPS topologies are Double-Conversion True Online and Standby / Eco. Many quality-based considerations are involved when choosing the the optimal UPS for the job, like how they are coping with voltage disturbances.
- Double-conversion (Online)
- Output power capacityThe maximum power that the device can produce.
- 6 kVA
- Output powerThe power that the device can produce.
- 5400 W
- Compliance certificatesIndicates which regulatory, safety, and environmental standards the product complies with, as verified by recognized authorities or certification bodies.
- RoHS
- Rack mount kitIndicates whether the necessary hardware is included to install the unit into a standard 19-inch equipment rack.
- Yes
- Cables includedSpecifies the types and quantities of connection cables provided with the product (e.g., 3.5 mm to 3.5 mm or SATA).
- Phone (RJ-11), Serial, USB cable
- Quick installation guideIndicates whether a simplified, fast-start manual is included with the product.
- Yes
- SafetyList of regulatory safety standards for all countries in which this product has been certified.
- UL 1778 5th Ed., CSA C22.2 NO.107.3-05, FCC 15 A
Show all 68 specificationsShow key specifications only
Design
- Form factorThe shape or design of the product.
- Rackmount/Tower
- Product colourThe colour e.g. red, blue, green, black, white.
- Black
- Housing materialWhat the casing of the product is made of.
- Steel
- LED indicatorsThe specific status lights available on the unit to provide visual feedback on its current state or connectivity (e.g., AC input, ACT, or Access).
- Yes
Features
- UPS topologyThe two main UPS topologies are Double-Conversion True Online and Standby / Eco. Many quality-based considerations are involved when choosing the the optimal UPS for the job, like how they are coping with voltage disturbances.
- Double-conversion (Online)
- Output power capacityThe maximum power that the device can produce.
- 6 kVA
- Output powerThe power that the device can produce.
- 5400 W
- Rack capacityThe spase that device fill in rack.
- 8U
- Cable lengthHow long the cable is.
- 3 m
- WaveformThe shape and characteristics of the electrical signal produced or measured by the device (e.g. Pure sine or Biphasic truncated exponential).
- Sine
- Input operation voltage (min)The minumum voltage needed by the device during operation.
- 120 V
- Input operation voltage (max)The maximum input voltage supported by the device.
- 280 V
- Input frequencyThe frequency (Hz) which is required to power the product.
- 40 - 70 Hz
- Output operation voltage (min)The minumum voltage produced by the device during operation.
- 200 V
- Output operation voltage (max)The maximum output voltage produced by the device.
- 240 V
- Output frequencyThe frequency of the electrical current delivered by the device, measured in hertz (e.g. 47/53 Hz).
- 50/60 Hz
- Surge energy ratingA surge protector is an appliance designed to protect electrical devices from voltage spikes. A surge protector attempts to limit the voltage supplied to an electric device by either blocking or by shorting to ground any unwanted voltages above a safe threshold. The surge energy rating is a measure of how much energy a surge protector can theoretically absorb in a single event, without failure.
- 2430 J
- Transfer time (Line Mode to Battery Mode)The time required for the device to switch from mains power to battery power during a power failure, measured in ms.
- 0 ms
- Efficiency (ECO mode)The energy efficiency of the device when operating in its power-saving ECO mode, measured in %.
- 96%
- Input power factorThe ratio of the real power drawn from the source to the apparent power supplied, indicating the efficiency of power delivery.
- 0.99
- Output power factorThe ratio of the real power delivered to the load to the apparent power supplied by the device.
- 0.9
- Crest factorThe ratio of the peak current to the average current of the load, expressed as a proportion (e.g., 3:1).
- 3:1
- Overload capacity - line mode (1 minute)The maximum percentage of the rated load that the device can sustain for one minute while operating in line mode, measured in %.
- 125%
- EMI/RFI noise filteringThe level of electromagnetic interference and radio frequency interference attenuation provided by the device, measured in dB.
- Yes
- Audible alarm(s)Alarms that make a sound when they are activated (set off).
- Yes
- Audible alarm modesThe specific conditions or system states that trigger an audible warning signal, such as a low battery or an overload event.
- Alarm when on battery, Fault, Low battery alarm, Overload alarm
- Socket circuit breakerIndicates whether the unit includes a dedicated circuit breaker for protecting socket outlets.
- Yes
Weight & dimensions
- WidthThe measurement or extent of something from side to side.
- 433 mm
- DepthThe distance from the front to the back of something.
- 660 mm
- HeightThe measurement of the product from head to foot or from base to top.
- 355.6 mm
- WeightWeight of the product without packaging (net weight). If possible, the net weight is given including standard accessories and supplies. Please note that sometimes the manufacturer leaves out the weight of accessories and/or supplies.
- 144.4 kg
Certificates
- Compliance certificatesIndicates which regulatory, safety, and environmental standards the product complies with, as verified by recognized authorities or certification bodies.
- RoHS
Packaging content
- Rack mount kitIndicates whether the necessary hardware is included to install the unit into a standard 19-inch equipment rack.
- Yes
- Cables includedSpecifies the types and quantities of connection cables provided with the product (e.g., 3.5 mm to 3.5 mm or SATA).
- Phone (RJ-11), Serial, USB cable
- Quick installation guideIndicates whether a simplified, fast-start manual is included with the product.
- Yes
Safety regulation & standards
- SafetyList of regulatory safety standards for all countries in which this product has been certified.
- UL 1778 5th Ed., CSA C22.2 NO.107.3-05, FCC 15 A
Operational conditions
- Operating temperature (T-T)The minimum and maximum temperatures at which the product can be safely operated.
- 0 - 40 °C
- Storage temperature (T-T)The minimum and maximum temperatures at which the product can be safely stored.
- -20 - 45 °C
- Operating relative humidity (H-H)The range of relative humidity, expressed as a percentage, within which the device can function correctly without damage or performance loss.
- 0 - 90%
- Storage relative humidity (H-H)The permissible range of relative humidity, expressed as a percentage, within which the product can be stored without damage.
- 0 - 95%
- Operating altitudeThe maximum and minimum height above sea level at which the device can function correctly, measured in m.
- 0 - 3000 m
- Non-operating altitudeThe maximum and minimum altitude at which the unit can be stored or transported without sustaining damage, measured in metres.
- 0 - 15000 m
Display
- Display typeType of display (screen) e.g. LCD.
- LCD
Battery
- Battery technologyThe type of battery in the device, e.g. nickel–cadmium (NiCd).
- Sealed Lead Acid (VRLA)
- Battery capacityA measure of the charge stored by the battery. Determined by the mass of active material contained in the battery.
- 7 Ah
- Battery voltageThe voltage (V) of the battery.
- 12 V
- Typical backup time at full loadThe amount of time that a backup energy source (e.g. UPS - Uninterruptible Power Source) can power the device for, when the backup energy source is fully loaded (100% of capacity).
- 5.4 min
- Typical backup time at half loadThe amount of time that a backup energy source (e.g. UPS - Uninterruptible Power Source) can power the device for, when the backup energy source is half-loaded (50% of capacity).
- 15 min
- Hot-swap batteryIndicates whether the battery can be replaced while the unit remains powered on and operational.
- Yes
- Cold startIndicates whether the unit can be started or operated correctly under specific initial conditions, such as very low temperatures or without an external power source.
- Yes
Power
- Number of batteries supportedThe number of batteries that can be used with the product.
- 20
Ports & interfaces
- AC outlet typesThe type of outlet for AC electricity.
- NEMA 5–20R, NEMA L6-20R, NEMA L6-30R
- Power plugA power plug is a 2 or 3 pinned device that is placed into an electrical socket in order to make an electrical connection.
- NEMA L6-30P
- AC outlets quantityThe number of sockets in the device where AC electrical power can be connected.
- 10 AC outlet(s)
- USB portThe device features a socket into which a USB cable can be plugged.
- Yes
- USB 2.0 ports quantityNumber of USB 2.0 ports (connecting interfaces) in the device. USB 2.0 was released in April 2000 (now called "Hi-Speed"), adding higher maximum signaling rate of 480 Mbit/s (effective throughput up to 35 MB/s or 280 Mbit/s), USB 2.0 ports are usually black.
- 1
- USB port typeThe physical interface standard of the USB connector used for connectivity or charging (e.g. USB-C).
- USB Type-B
- Serial interfaceIndicates whether the device features a serial port for communication and management purposes.
- Yes
- Serial interface typeThe physical connector standard used for the serial communication port (e.g. DB9 or RJ-45).
- RS-232
- Serial ports quantityThe number of serial ports in a computer or peripheral. A serial port is a serial communication physical interface through which information transfers in or out one bit at a time. The term "serial port" usually identifies hardware more or less compliant to the RS-232 standard, intended to interface with a modem or with a similar communication device. In modern computers and peripherals, serial po…
- 1
- Modem (RJ-11) portsThe number of available RJ-11 connectors used for connecting telephone lines to the device.
- 2
- Ethernet LAN (RJ-45) portsNumber of Ethernet LAN (RJ-45) ports (connecting interfaces) in the device. Ethernet LAN (RJ-45) ports allow a computer to connect to the ethernet.
- 2
Management features
- ECO modeIndicates whether the device features an energy-saving mode to reduce power consumption during operation.
- Yes
Performance
- Noise levelThe amplitude level of the undesired background noise, usually measured in decibels (db).
- 65 dB
Packaging data
- Package widthThe distance from one side of the packaging to the other.
- 600 mm
- Package depthThe distance from the front to the back of the packaging.
- 900 mm
- Package heightThe distance from the top to the bottom of the packaging.
- 968 mm
- Package weightWeight of the packaged product.
- 186 kg
Database Right data-sheet 2026 Icecat. All rights reserved. Provided “as is”, without warranty — check details with the store before buying.
Price history (90 days, best daily price)
Price history is still being collected for this product — check back soon.
Alternative models

CyberPower UT1050EI uninterruptible power supply (UPS) Line-Interactive 1.05 kVA
630 W 4 AC outlet(s)

CyberPower OL6KRT uninterruptible power supply (UPS) Double-conversion (Online) 6 kVA
5400 W 4 AC outlet(s)

CyberPower OLS1000 uninterruptible power supply (UPS) Double-conversion (Online) 1 kVA
900 W 4 AC outlet(s)

CyberPower M750L uninterruptible power supply (UPS) Line-Interactive 0.75 kVA
600 W 6 AC outlet(s)

CyberPower OL10KRTHW uninterruptible power supply (UPS) Double-conversion (Online) 10 kVA
10000 W 1 AC outlet(s)

CyberPower M550L uninterruptible power supply (UPS) Line-Interactive 0.55 kVA
440 W 4 AC outlet(s)